Provide Peace of Mind to Occupants with an IndoorAir Quality Assessment & Certification

Survey

Information is gathered about your space to uncover latent and apparent risk factors that can identify where a more in-depth focus is needed to help tailor corrective actions

Mold, Moisture & Humidity

Robust testing and analysis can identify the root cause of moisture and mold to ensure proper remediation and resolution

TVOCS, CO, NO2, Ozone

Cleaning chemicals, building materials, and combustion appliances create unhealthy IAQ. This has a variety of adverse outcomes from impaired cognitive function to headaches and irritation

Particulate Matter

PM 2.5 are microscopic particles (virus, bacteria, dust). Elevated levels can indicate an unhealthy building which needs filtration improvements or revised cleaning products

Ventilation (CO2)

Improper air exchange results in increased viral load (if lacking) and high operating costs (if excessive). We help buildings determine their air changes per hour (ACH) by conducting ventilation studies

Scorecard & Testing Plaque

Our scorecard/report provides a corrective action roadmap for how to prioritize indoor environmental quality investments. The plaque demonstrates your commitment to improving conditions

Clean Indoor Air Matters

Launched March 2022, the EPA’s “Clean Air In Buildings Challenge” is a call to action to building owners and operators to meet recommended guidelines to improve indoor air quality & protect public health.

Here are the benefits of Donnelly Mechancial’s Indoor Air Quality Assesment & Certification, partnered with Indoor Science

  • Plaque in as Little as 2 Weeks from Project Initiation
  • Performed by Credentialed Experts
  • Industry Best Practices & Regulatory Guidelines
  • Cost Effective & Transparent Pricing
  • Scientific Grade Instruments & Lab Testing
  • Full Building or Occupant Spaces

Our Indoor Air Quality services can help to find a good balance between energy efficiency, comfort and overall indoor air quality.

Instruments, Test Methods & Criteria for Achieving Certification

Category Instrument Method Passing Criteria
CategoryMold, Moisture, Humidity InstrumentInfrared Camera
Dial-mode Moisture Meter
Thermo-Hygrometer Spore Traps & Air Pump Tape-lift kits
MethodIR,& moisture analysis of full space RH Measurements Air/surface samples in areas of suspect microbial growth Passing CriteriaNo visible mold growth RH between 40%-60% If air samples are collected, indoors similar to outdoors (or less)
CategoryTVOCs, CO, NO2, Ozone InstrumentPhotoionization detector
Electrochemical Sensors
Continuous IAQ Monitor
Method1 reading every 1,000 SF using a 1-minute average
or
1 month of temporary IAQ monitoring with minimum of 1 sensor every 10,000 SF
Passing CriteriaTVOC < 3,000 µg/m3
CO < 2ppm above outdoors
NO2 < 53 ppb
Ozone < 70 ppb
CategoryParticulate Matter (PM2.5) Instrument6-Channel Optical Particle Counter or Nephelometer
Continuous IAQ Monitor
Method1 reading every 1,000 SF using a 1-minute average
or
1 month of temporary IAQ monitoring with minimum of 1 sensor every 10,000 SF
Passing CriteriaPM2.5 < 12 µg/m3
CategoryVentilation (CO2) InstrumentNDIR Calibrated Sensor
Continuous IAQ Monitor
Method1 reading every 1,000 SF using a 1-minute average
or
1 month of temporary IAQ monitoring with minimum of 1 sensor every 10,000 SF
Passing CriteriaCO2 < 1,000 ppm

Steps to achieve your assessment & certification

Complete Intake Form
Schedule Site Visit for Field Work
Receive Corrective Action Report
Receive Certificate of Testing Plaque
Make verified Corrective Action
Receive Certificate of Passing Plaque

Want to download this PDF?

Download Now

Talk with us about
Commercial HVAC

Fast Response and a Worry-Free Resolution

(718) 886-1500