Provide Peace of Mind to Occupants with an IndoorAir Quality Assessment & Certification
Survey
Information is gathered about your space to uncover latent and apparent risk factors that can identify where a more in-depth focus is needed to help tailor corrective actionsMold, Moisture & Humidity
Robust testing and analysis can identify the root cause of moisture and mold to ensure proper remediation and resolutionTVOCS, CO, NO2, Ozone
Cleaning chemicals, building materials, and combustion appliances create unhealthy IAQ. This has a variety of adverse outcomes from impaired cognitive function to headaches and irritationParticulate Matter
PM 2.5 are microscopic particles (virus, bacteria, dust). Elevated levels can indicate an unhealthy building which needs filtration improvements or revised cleaning productsVentilation (CO2)
Improper air exchange results in increased viral load (if lacking) and high operating costs (if excessive). We help buildings determine their air changes per hour (ACH) by conducting ventilation studiesScorecard & Testing Plaque
Our scorecard/report provides a corrective action roadmap for how to prioritize indoor environmental quality investments. The plaque demonstrates your commitment to improving conditionsClean Indoor Air Matters
Launched March 2022, the EPA’s “Clean Air In Buildings Challenge” is a call to action to building owners and operators to meet recommended guidelines to improve indoor air quality & protect public health.
Here are the benefits of Donnelly Mechancial’s Indoor Air Quality Assesment & Certification, partnered with Indoor Science
- Plaque in as Little as 2 Weeks from Project Initiation
- Performed by Credentialed Experts
- Industry Best Practices & Regulatory Guidelines
- Cost Effective & Transparent Pricing
- Scientific Grade Instruments & Lab Testing
- Full Building or Occupant Spaces
Our Indoor Air Quality services can help to find a good balance between energy efficiency, comfort and overall indoor air quality.
Instruments, Test Methods & Criteria for Achieving Certification
Category | Instrument | Method | Passing Criteria |
---|---|---|---|
CategoryMold, Moisture, Humidity | InstrumentInfrared Camera Dial-mode Moisture Meter Thermo-Hygrometer Spore Traps & Air Pump Tape-lift kits |
MethodIR,& moisture analysis of full space RH Measurements Air/surface samples in areas of suspect microbial growth | Passing CriteriaNo visible mold growth RH between 40%-60% If air samples are collected, indoors similar to outdoors (or less) |
CategoryTVOCs, CO, NO2, Ozone | InstrumentPhotoionization detector Electrochemical Sensors Continuous IAQ Monitor |
Method1 reading every 1,000 SF using a 1-minute average or 1 month of temporary IAQ monitoring with minimum of 1 sensor every 10,000 SF |
Passing CriteriaTVOC < 3,000 µg/m3 CO < 2ppm above outdoors NO2 < 53 ppb Ozone < 70 ppb |
CategoryParticulate Matter (PM2.5) | Instrument6-Channel Optical Particle Counter or Nephelometer Continuous IAQ Monitor |
Method1 reading every 1,000 SF using a 1-minute average or 1 month of temporary IAQ monitoring with minimum of 1 sensor every 10,000 SF |
Passing CriteriaPM2.5 < 12 µg/m3 |
CategoryVentilation (CO2) | InstrumentNDIR Calibrated Sensor Continuous IAQ Monitor |
Method1 reading every 1,000 SF using a 1-minute average or 1 month of temporary IAQ monitoring with minimum of 1 sensor every 10,000 SF |
Passing CriteriaCO2 < 1,000 ppm |
Steps to achieve your assessment & certification
Complete Intake Form
Schedule Site Visit for Field Work
Receive Corrective Action Report
Receive Certificate of Testing Plaque
Make verified Corrective Action
Receive Certificate of Passing Plaque
Want to download this PDF?
Download NowTalk with us about
Commercial HVAC
Fast Response and a Worry-Free Resolution
(718) 886-1500